01

PRODUCT

Number of views:
1033

CWX-60P

Large torque electric valve Torque-6.0NM  On/off time <8S
Retail price
0.0
Market price
0.0
Number of views:
1033
Product serial number
产品介绍:
Quantity
-
+
Stock:
Product description
Parameters
Technology Specification
Schematic Diagram and Sizes
Wiring Diagram

Product Series:CWX

Product Name:CWX-60P

 

 

★ Can work in boiler water room, good substitution for solenoid valve

1、Metal gearbox and metal gear design, low noise, perform reliably

2、Long service life: more than 100000 circles

3、Electric limit and machinery limit design, located accurately, avoid gear run continuously. 

4、Mufti-angle assembling, easy to install

5、Float ball structure, no leakage,especially suitable for heavy pollution conditions.

 

 

1. IC card smart meter, heat meter

2. HVAC andfan coil, fire sprinkler, etc.

3. Universities water, automatic control systems, industrial automation and other small devices

4. Environmental protection, water supply and drainage, water treatment works

5. Replace the solenoid valve where can not working

6. The water-saving appliances, equipment and other drinking water

We could not find any corresponding parameters, please add them to the properties table

 

 

Product model

 

 

Rated voltage

 

 

Working current

 

 

Output torque

 

 

Open/close time

 

 

Control mode

 

 

DN8-32

 

 

DC3-6V
DC12V
AC/DC9-24V
AC220V
AC85-265V

 

 

Max100mA(CR04

except Max150mA)

 

 

 

Max6NM

 

 

<8s

 

 

CR01   CR02 CR02+

 CR03 CR03A CR03T

CR04  CR05 CR06

 

 

 

Working pressure

 

 

Power

 

 

Medium temperature

 

 

Size

 

 

IP Garde

 

 

Special function

 

Max1.0Mpa <5W 0-90℃

DN8-32 Two-way

DN8-25Three-way 

IP65

CR01 CR02 CR02+ CR03 CR03A

CR04(can with singal feedback)

 

 

 

 

Brass Connection Size d L H W
Both female thread full port          DN8 8 46 31 0.402
DN15 15 57 38 0.478
DN20 20 71 45 0.559
DN25 23.5 72 49 0.648
Both female thread reduce port DN10 8 46 31 0.401
DN20 15 66 38 0.493
DN25 20 72 47 0.653
DN32 25 86 60 0.865
3-way vertical DN15 12 63 49 0.48
DN20 15 66 53 0.537
CPVC Both female thread DN15 15 60 47 0.357
DN20 20 72 51 0.385

 

 

Brass          Connection Size d L H W
Female-male thread full port DN15 15 63 38 0.477
Female-male thread reduce port DN20 15 66 38 0.507
DN25 15 81 44 0.694
DN32 20 76 50 0.739
Both male thread DN15 15 68 38 0.469
Stainless steel Both female thread full port          DN8 8 46 31 0.409
DN15 15 55 38 0.485
DN20 20 71 45 0.553
DN25 25 72 49 0.662
Both female thread reduce port DN10 8 46 30.5 0.413
DN20 15 63 39 0.558
DN25 20 75 47 0.653

 

 

3-way horizontal     (brass)  Size d L1 L2 H W
DN8 6 52.6 39 24.5 0.414
DN15 12 72 55 39 0.739
DN20 15 86 63.5 44  
DN25 15 97 68.5 43.5  

 

 

Valve body

 

 

Sealing

 

 

Seat

 

 

Valve ball

 

Brass/Nickel plated
Brass/SS304 316

 

Silicon Rubber/NBR/EPDM

 

PTFE Brass/SS304 316

 

 


      CR01 wiring diagram (two wires and reverse polarity)

      Volt:DC3-6V,12V,24V

      1. Connecting SW and OPEN, the valve opens,getting the
      position,automatically power off,the valve remains fully open
      position.
      2. Connecting SW and ClOSE, the valve close,getting the
      position,automatically power off,the valve remains fully close
      position 
 

      CR02 wiring diagram (three wires two point control)

      Volt:DC3-6V,12V,24V
      1. Connecting SW and OPEN, the valve opens,getting the
      position,automatically power off,the valve remains fully open
      position.
      2. Connecting SW and ClOSE, the valve close,getting the
      position,automatically power off,the valve remains fully close
      position 
 

 

      CR02+ wiring diagram(three wires&fail-safe/power-off return) 

      Voltage:DC9-24V  

      1.Connecting SW to OPEN, the valve opens , getting the
      position and automatically,power off, the valve remains
      fully open position
      2.Disconnecting SW to CLOSE, the valve close , getting the
      position and automatically power off, the valve remains
      fully close position
      Note:As the power-off and valve will be return automatically,
      and RD/G(B)/Y(B) 3wires can not be power-on together to
      keep valve safe
 

      CR03 wiring diagram(three wires one point control)

      Voltage:DC3-6V/12V /ADC9-24V /AC220V
      1.Connecting SW, the valve opens , getting the position
      ,automatically power off, the valve remains fully open position
      2.Disconnecting SW, the valve close , getting the position
      ,automatically power off, the valve remains fully close
      position
      Note:When power is DC voltage and Red Wires is “+”,
      Blue wire is “—”
 
 
 

 

      CR03T wiring diagram (angle adjustable) 

      Voltage DC9-24V

      1.SW1 open, SW2 open, valve full close, getting the position
      valve remains fully close position
      2.SW1 close, SW2 open,valve open 30 degree, getting
      the position valve remains open 30 degree position
      3.SW2 close, SW1 open,valve open 60 degree, getting
      the position valve remains open 60 degree position
      4.SW1 close, SW2 close, valve full open, getting the position
      valve remains fully open position
 

      CR03A wiring diagram ( three wires one point control with “-“)  

      Voltage ADC9-24V
      1.Connecting SW, the valve opens, getting the position,
      automatically power off, the valve remains fully open position
      2.Disconnecting SW, the valve close, getting the position,
      automatically power off, the valve remains fully close position
 
 
 

 

      CR04 wiring diagram(two wires and fail-safe/power-off return) 

      Voltage:DC3-6V/ADC9-24V/AC220V

      1.SW connecting ,the valve open, getting the position and the
      power off automatically,the valve remains fully open/close
      position
      2.SW disconnecting ,the valve close, getting the position and
      power off automatically,the valve remains fully open/close
      position
 
 
 
 
 
 

      CR05 wiring diagram (five wires with signal feedback)

      Voltage:DC3-6V/12V/24V

     1.Connecting SW and OPEN , the valve opens , getting the
       position green  wire output the OLS signal , the controller
       test the signal OLS, connectSW to STOP, the valve stops and
       remains fully open position
     2.Connecting SW and CLOSE , the valve close , getting the
       position red wire output the CLS signal , the controller test
       the signal CLS, connect SW to STOP, the valve stops and remains
       fully close position,
  Note:Please make sure the signal wires "red","black" and
       "green" be connected at first,then connect the power wires "              yellow" and"blue"

 

      CR06 wiring diagram (five wires)   

      Volt:AC220V 

      1. Connecting SW and OPEN,the valve opens,getting the
      position,automatically power off,the valve remains fully open
      position.
      2. Connecting SW and CLOSE,the valve close,getting the
      position,automatically power off,the valve remains fully
      close position.
 

      CR01S wiring diagram (five wires with feedback)   

      Voltage DC3-6V,12V,24V
     1.Connecting SW to OPEN, the valve opens, getting the position,
     automatically power off, the valve remain fully open position,
     meanwhile output open position signal
     2.Connecting SW to CLOSE, the valve close, getting the position,
     automatically power off, the valve remains fully close position,
     meanwhile output close position signal

 

      CR02S wiring diagram (six wires with feedback)

      Voltage DC3-6V,12V,24V

      1.Connecting SW to OPEN, the valve opens, getting the position,
      automatically power off, the valve remains fully open position,
      meanwhile output open position signal

      2.Connecting SW to CLOSE, the valve close, getting the position,
      automatically power off, the valve remains fully close position,
      meanwhile output close position signal

 

 

 

      CR03S wiring diagram (six wires with feedback)   

      Voltage DC3-6V/ADC9-24V/AC220V
      1.Connecting SW, the valve opens, getting the position,
      automatically power off, the valve remains fully open position,
      meanwhile output open position signal
      2.Disconnecting SW, the valve close, getting the position,
      automatically power off, the valve remains fully close position,
      meanwhile output close position signal
      Notes: When power is DC voltage and Red Wires is “+”,
      Blue wire is “-“
 

 

      CR04S wiring diagram (five wires with feedback)

      Voltage ADC9-24V/AC220V
      1.SW connecting, the valve open, getting the position and
      the power off automatically, the valve remains fully open/close
      position, meanwhile output open position signal
      2.SW disconnecting, the valve close, getting the position
      and the power off automatically, the valve remains fully
      open/close position, meanwhile output close position signal

 

     

 

 

 